dc.identifier.citation POPESCU, Mihaela, BITOLEANU, Alexandru, SURU, Vlad et al. Increasing Power Quality in a 6-pulse DC-Traction Substation [Resursă electronică]. In: SIELMEN 2017: Proceedings of the 11-th international conference on electromechanical and power systems, 11-13 octombrie, 2017. Chișinău, 2017, pp. 518-523. ISBN 978-1-5386-1846-2. en_US
dc.identifier.isbn 978-1-5386-1846-2
dc.identifier.uri http://repository.utm.md/handle/5014/7183
dc.description Abstract & References en_US
dc.description.abstract This paper presents an active DC-traction substation with six-pulse uncontrolled rectifier, whose structure and control ensure the braking energy recovery and increased power quality in both traction and regeneration regimes. The key component in the power structure is a voltage source inverterbased shunt active power filter connected properly between the DC-traction line and the power supply. To meet the goal of unity power factor at the power supply side, the current provided by the inverter is indirectly controlled through the supply current. In the generation of the reference current, the adopted algorithm involves the intermediate transformation of the currents’ threephase system into a rotating phasor synchronous with the voltage space phasor. A dedicated Matlab-Simulink has been conceived for the whole system. The results of the simulation show that, during the traction regime, the shunt active power filter succeeds in injecting the proper required currents in the point of common coupling, so that almost sinusoidal currents are drawn from the power supply under unity power factor. During the regeneration regime, the voltage source inverter injects active power into the power supply, also under almost unity power factor conditions. en_US
dc.language.iso en en_US
dc.publisher Institute of Electrical and Electronics Engineers en_US
dc.rights Attribution-NonCommercial-NoDerivs 3.0 United States *
dc.rights.uri http://creativecommons.org/licenses/by-nc-nd/3.0/us/ *
dc.subject active power filters en_US
dc.subject filters en_US
dc.subject DC-traction en_US
dc.subject harmonics en_US
dc.subject reactive power en_US
dc.title Increasing Power Quality in a 6-pulse DC-Traction Substation en_US
dc.type Article en_US


Files in this item

The following license files are associated with this item:

This item appears in the following Collection(s)

  • 2017
    11-13 Oct. 2017

Show simple item record

Attribution-NonCommercial-NoDerivs 3.0 United States Except where otherwise noted, this item's license is described as Attribution-NonCommercial-NoDerivs 3.0 United States

Search DSpace


Advanced Search

Browse

My Account